5 Test of Current Transformer

Introduction

Current transformers (CTs) are vital in power systems. They ensure accurate measurement and monitoring of electrical currents. They protect high-voltage systems by reducing currents to safer, measurable levels. These can be handled by metering and protective equipment. These devices are vital for power distribution and transmission. So, we must ensure they work properly. Regular testing of current transformers ensures their reliability and accuracy. It prevents system failures, equipment damage, and hazardous situations.

This article will explore tests for assessing current transformers. It will cover the equipment used and the need to test it. This is to ensure safe, efficient power systems. We’ll cover everything you need to know. From routine checks, like the CT ratio and polarity tests, to specialized procedures. They will ensure your CTs are in top condition.

Why the testing of current transformers is essential

The importance of testing current transformers cannot be overstated. These devices are responsible for accurate measurements, protection, and control in power systems. If they fail to work correctly, the results can be severe. They include incorrect power metering, undetected faults, and safety risks. Regular testing ensures that CTs are accurate and reliable. It also ensures compliance with international standards, like IEC 61869-2 and IEEE C57.13.

Here’s why testing is crucial:

  • Accuracy: A miscalibrated CT could cause erroneous data. This could affect billing in metering apps and malfunction protection systems.

  • Safety: Faulty CTs could result in equipment damage or system-wide power outages. Identifying potential issues through testing ensures safe operation.

  • Compliance: Industry rules require all electrical systems, including current transformers, to meet certain standards. Testing helps confirm that your CTs meet these critical standards.

Types of Current Transformer Tests

There are several testing methodologies for assessing the condition and performance of CTs.

Routine Test of Current Transformer:

  • These tests are done during manufacturing and after installation. They ensure the transformer works before it is put into service. Routine tests include polarity tests, ratio tests, and insulation resistance tests.

Type Test of Current Transformer:

  • These tests are more comprehensive. They are done on a specific CT model or design. This ensures they can perform under various conditions. These tests include the temperature rise test, short-time current test, and accuracy test.

Special Test of Current Transformer:

  • Special tests are done under unique conditions. They are for specific transformers with concerns. Examples include partial discharge tests, impulse voltage tests, and dielectric power factor tests.

Routine Testing Procedures

Polarity Test of Current Transformer

Importance of Polarity in CT Connections

Polarity is critical in current transformers (CTs). It ensures the correct phase relationship between the primary and secondary currents. In metering and protection systems, wrong polarity can cause two issues. It can lead to inaccurate current measurements. It can also cause protective relays to fail. In a differential protection scheme, reversing the CT polarity may cause the relay to fail during a fault. This could damage equipment or create unsafe conditions. Correct polarity ensures the CT’s secondary current is in phase with the primary current. This allows the system to function accurately and safely.

In simple terms, a CT’s polarity shows the current flow in its primary winding. It indicates the direction of the current in the secondary winding. The CT usually has markings like P1/P2 on the primary side and S1/S2 on the secondary side to denote polarity. For correct operation, the current entering P1 must equal the current exiting S1 in the secondary circuit.

Test of Current Transformer

How to Conduct a Polarity Test

The polarity test is a simple way to check the current transformer’s polarity. The process involves applying a low DC voltage to the primary side. Then, measure the current on the secondary side to verify the flow direction.

Here’s a step-by-step procedure for performing the polarity test:

  • Disconnect the CT: Before testing, disconnect the current transformer from any live circuit or load.

  • Connect a DC source to the primary: Apply a small DC voltage or current to the primary winding terminals (P1 and P2). Typically, a battery (1.5V to 9V) is used as a DC source.

  • Use a voltmeter or ammeter to measure the output on the secondary terminals (S1 and S2) while applying the DC voltage.

    • If the current flows from S1 to S2 (matching the polarity markings), then the polarity is correct.

    • If the current flows from S2 to S1, the polarity is reversed.

  • Interpret the Results: A positive deflection in the ammeter or voltmeter confirms that the polarity is correct (P1 to S1, and P2 to S2). A negative deflection or opposite reading means the polarity is wrong. You may need to adjust the connections.

Tools and Instruments Required

To conduct a polarity test, you will need the following tools and instruments:

  • Low Voltage DC Source: A battery (1.5V to 9V) is commonly used for this purpose.

  • Digital Multimeter or Voltmeter: Use it to measure the voltage or current on the CT’s secondary side.

  • Ammeter: An ammeter can measure the secondary current and check the flow direction.

  • Test leads: High-quality test leads are vital. They connect the DC source, the CT, and the measuring devices.

  • Safety Equipment: Use insulated gloves, safety goggles, and other standard PPE to ensure safety during the test.

Ratio Test of Current Transformer

Explanation of the Current Transformation Ratio

The current transformation ratio is a key parameter of a CT. It defines the relationship between the primary current and the secondary current. The primary current is the current in the high-voltage primary winding. The secondary current is the stepped-down current in the secondary winding. This ratio is vital. CTs step down high currents for meters and protection devices.

For example, a CT with a 1000:5 ratio will step down 1000A on the primary side to 5A on the secondary side. The CT’s accuracy depends on keeping this ratio within the allowed range. Any deviation from the expected ratio can lead to inaccurate current measurement. This can affect the performance of relays, meters, and other equipment.

The ratio is given by the formula:

Transformation Ratio= Primary Current (I₁)/Secondary Current (I₂)

Test of Current Transformer

Step-by-Step Procedure for Performing a Ratio Test

The ratio test checks that the CT transforms the primary current to the secondary current at its rated ratio. Here’s how to perform the test:

Prepare the test setup:

    • Isolate the current transformer from the system.

    • Ensure the CT is disconnected from any load or circuit.

    • Gather the test equipment. It should include a current injection device, an ammeter, and test leads.

Inject Known Current into the Primary Winding:

    • Use a primary current injection test set to inject a known current into the primary winding of the CT. For example, if you want to test a CT with a 1000:5 ratio, you might inject 100A into the primary side.

Measure the secondary current:

    • Connect an ammeter to the CT’s secondary terminals (S1 and S2). Then, measure the secondary current from the injected primary current. Ensure the ammeter is set to measure in amperes (A) for accurate readings.

Calculate the Transformation Ratio:

  • Use the measured secondary current and the known injected primary current to calculate the transformation ratio.

Actual Ratio= Injected Primary Current/Measured Secondary Current

Repeat the test for multiple current levels:

    • To ensure accuracy, repeat the test at different primary current levels. Use 25%, 50%, 100%, and 120% of the rated primary current. This will confirm that the CT is accurate at all operating levels.

Interpreting the results

After the test, compare the actual ratio with the CT’s rated ratio (as per the manufacturer). Here’s how to interpret the results:

  1. Acceptable Tolerance Range:

    • The actual ratio must be within a tolerance range of the rated transformation ratio. This tolerance is usually specified in the CT’s accuracy class. For example, for a Class 0.5 CT, the ratio error should not exceed 0.5% at the rated current.

  2. Identifying Errors:

    • If the transformation ratio deviates from the rated ratio, the CT may have an issue, such as:

      • Winding defects: Faulty or deteriorated windings can cause errors in current transformation.

      • Magnetic saturation: A saturated core can distort ratio measurements at high currents.

      • Mechanical damage: Physical damage to the CT can result in incorrect transformation ratios.

  3. Corrective Action:

  • If the ratio error is too high, the CT may need recalibration, repair, or replacement to meet accuracy standards. For protection systems, especially differentials, small ratio errors can cause wrong relay operation. So, it’s vital to address these issues promptly.

Insulation Resistance Test of Current Transformer

Why Insulation Resistance Is Critical

Insulation resistance is vital for a current transformer’s (CT) safety and reliability. In electrical systems, insulation is vital. It prevents short circuits, electric shocks, and equipment damage from unwanted current paths. Insulation in CTs can degrade over time. Causes include moisture, dirt, aging, and temperature changes. This degradation can lower insulation resistance. It harms the CT’s performance and system safety.

A low insulation resistance can lead to dangerous conditions, such as:

  • Leakage Current: Low insulation resistance can allow current to leak between the CT windings and the core, or to the ground. This poses a serious risk of equipment failure or fire.

  • Dielectric Breakdown: Reduced insulation raises the risk of dielectric breakdown. This is when the insulation fails under electrical stress, possibly causing short circuits.

  • Damage to Connected Equipment: Poor insulation in the CT can harm downstream devices, like meters and relays. It may cause false readings or failures.

Regular insulation resistance tests ensure the CT operates safely. They prevent electrical hazards in the system.

Procedure and Tools Used for Insulation Resistance Testing

The insulation resistance test uses an instrument called a megohmmeter, or “megger.” The test applies a high DC voltage across the insulation. It measures the resistance between different parts of the CT. This includes the windings, the core, and the windings to ground.

Here’s a step-by-step procedure for conducting an insulation resistance test on a CT:

  1. Disconnect the current transformer:

    • Ensure the CT is disconnected from any live circuit and de-energized. Isolate it from the system to prevent interference from other equipment.

  2. Prepare the Testing Area:

    • Test in a clean, dry area. Moisture can affect the results.

    • Use safety gear, such as gloves and goggles, as the megger generates high voltage.

  3. Select Test Points:

    • The insulation resistance is typically measured between the following points:

      • Primary Winding to Secondary Winding

      • Primary Winding to Ground

      • Secondary Winding to Ground

    • For CTs with multiple secondary windings, test each winding separately.

  4. Connect the Megger:

    • Connect the megger’s positive terminal to one test point (e.g., the primary winding). Connect the negative terminal to another point (e.g., ground).

    • Make sure the connections are secure and properly insulated to avoid inaccurate readings.

  5. Apply the Test Voltage:

    • Set the megger to the proper voltage for the CT being tested. It should be 500V to 5kV, depending on the CT’s voltage rating.

    • Apply the test voltage and measure the insulation resistance.

  6. Record the reading:

    • The megger will display the insulation resistance in megohms (MΩ). Record the readings for each set of test points.

    • Test all required points: primary to secondary, primary to ground, and secondary to ground.

Acceptable Values and Troubleshooting Tips

The acceptable insulation resistance values depend on the CT’s voltage rating and application. Generally, a healthy CT should have an insulation resistance value in the range of 100 MΩ or higher. Lower values could indicate potential insulation problems.

Here’s how to interpret the results:

  1. High Insulation Resistance (above 100 MΩ):

    • If the resistance is in the acceptable range, the CT’s insulation is likely in good condition.

    • Record the values. If possible, compare them with previous tests. This will track any changes in insulation over time.

  2. Low Insulation Resistance (below 100 MΩ):

    • If the insulation resistance is too low, it may mean: 1. The insulation is deteriorating. 2. Moisture has entered. 3. There is contamination.

    • Low values require immediate attention to prevent potential failure. Consider performing additional diagnostic tests to pinpoint the problem.

Troubleshooting Tips

  • Moisture in the CT: If moisture is suspected, dry the CT. Place it in a dry environment or use a controlled heat source. Afterward, retest the insulation resistance.

  • Surface Contamination: Dust and dirt on the CT’s surface can lower insulation resistance. Clean the CT with a dry, non-abrasive cloth before retesting.

  • Damaged Insulation: If repeated low readings occur, the insulation may be physically damaged. In such cases, the CT may need to be replaced, as damaged insulation cannot be repaired.

  • Aging: Insulation naturally degrades over time. Older CTs may show a slow drop in insulation resistance, even without damage. If the insulation resistance keeps dropping in tests, plan for maintenance or replacement.

Test of Current Transformer

Burden Test of Current Transformer

Definition of CT Burden and Its Impact on Performance

CT Burden is the total load on a current transformer’s (CT) secondary winding. It is expressed in ohms (Ω) or volt-amperes (VA). It includes all devices on the secondary side, like ammeters, relays, and other meters. The burden is crucial because it affects the accuracy and performance of the CT in several ways:

  1. Accuracy:

    • Each CT is designed to work with a specific burden. Connecting a load outside this range can cause measurement errors. If the burden is too low, the CT may not transform the primary current accurately. This could result in a higher-than-expected output. Conversely, a too-high burden can saturate the CT core. This also leads to inaccuracies.

  2. Saturation:

    • If the burden exceeds the rated value of the CT, the core may saturate under high current conditions. Saturation can prevent the CT from accurately transforming the current. This can distort measurements and cause protection relays to misoperate.

  3. Thermal Limits:

    • The burden affects the thermal performance of the CT. An excessive burden can overheat the CT. This can degrade its insulation and cause failure.

  4. Phase Shift:

    • Changes in load can shift the phase between the primary and secondary currents. This can affect the accuracy of power measurements and protective relaying.

In summary, we must manage a CT’s burden. It’s key to the accuracy and reliability of electrical systems.

How to Measure and Verify the Burden Rating

We need a systematic way to measure and verify the burden rating of a current transformer. It must assess the total load on the secondary winding. This load must be within the manufacturer’s specified limits. Here’s how to conduct a burden test:

  1. Identify the CT Burden Rating:

    • Before the test, check the manufacturer’s specs for the CT’s rated and max burdens (in VA). This information is crucial for comparison during the test.

  2. Disconnect the CT:

    • Ensure that the CT is disconnected from any live circuits and that it is de-energized. Safety precautions are vital to prevent electric shock or damage to the equipment.

  3. Connect Test Equipment:

    • Use a burden tester, which is specifically designed to apply a known load to the CT’s secondary winding. If a burden tester is not available, use resistive loads (like resistors) or a test load bank to create a burden.

    • Ensure that the burden test setup is rated for the expected current levels.

  4. Apply a known primary current:

    • Inject a known primary current into the CT using a current injection test set. This can be done at various levels to simulate real conditions. For example, 10%, 50%, and 100% of the CT’s rated primary current.

  5. Measure the secondary current:

    • Use an ammeter on the CT’s secondary terminals. Measure the secondary current from the injected primary current. Record these values for analysis.

  6. Calculate the Secondary Burden:

    • Determine the burden. Multiply the measured secondary current by the load resistance connected to the secondary.

    Burden (VA) = Secondary Current (I₂) × Voltage across the burden (V)

    • If you’re using resistive loads, the voltage can be calculated as:

    V = I₂ × RV = I₂ × RV

    where RRR is the total resistance of the load.

  7. Compare with Manufacturer’s Ratings:

    • After calculating the burden, compare it to the manufacturer’s rating. Ensure that it falls within the specified limits.

  8. Assess the performance:

    • If the burden is within acceptable limits, the CT is functioning as expected. If the burden exceeds the rated value, take corrective action. Reduce the load or use a CT with a higher rating.

Acceptable Values and Troubleshooting Tips

  1. Acceptable Values:

    • The acceptable burden rating will vary by CT model and application. A typical burden rating for protection CTs might range from 2 to 15 VA. Always consult the CT’s datasheet for specific limits.

  2. Troubleshooting Tips:

  • If you find that the burden exceeds the rated value, investigate the following:

  • Connected Devices: Do not connect any unnecessary devices to the CT’s secondary side.

  • Additional Loads: Check for any changes in connected loads since the last test.

  • Calibration of Measurement Tools: Check that your tools are calibrated and working. This will avoid incorrect readings.

  • Use of Correct CT: If the app needs more than the CT can provide, consider upgrading to a higher-capacity CT.

Excitation Test of Current Transformer

Purpose of the Excitation or Magnetization Curve

The excitation test of Current Transformer, or magnetization test, is done on current transformers (CTs) to find their magnetization curve. This curve is key to understanding the CT core’s magnetic behavior. It is essential for several reasons:

  1. Core Characteristics:

    • The excitation curve shows how the applied voltage affects the magnetizing current. It shows the material’s properties and its response to different magnetic field strengths.

  2. Saturation Point:

    • One of the primary purposes of the excitation test of Current Transformer is to identify the saturation point of the CT core. The saturation point indicates the maximum level of magnetization the core can achieve. Beyond this point, higher input current won’t increase output. This will cause measurement errors.

  3. Performance Assessment:

    • The excitation curve helps assess the overall performance and efficiency of the CT. A steep curve indicates good performance. A flat curve may suggest issues, such as core damage or degradation.

  4. Design Validation:

    • For manufacturers, the excitation curve is vital. It validates the design and ensures the CT meets specifications. It can also be used for quality control during manufacturing.

  5. System Protection:

    • Understanding the excitation characteristics is important for relay settings and system protection schemes. A CT that saturates too easily could cause incorrect relay operation during faults.

How to Conduct an Excitation Test

An excitation test of Current Transformer applies a controlled voltage to the CT. It measures the resulting magnetizing current. Here’s a step-by-step guide on how to perform the test of Current Transformer:

  1. Disconnect the CT:

    • Ensure the current transformer is disconnected from any live circuits and is de-energized. Safety is paramount, so use appropriate personal protective equipment (PPE).

  2. Connect the test equipment:

    • Use a variable AC power supply to apply voltage to the primary winding of the CT. Connect an ammeter in series with the CT to measure the magnetizing current. You may also need a voltmeter to measure the voltage applied to the primary winding.

  3. Apply Voltage:

    • Gradually increase the voltage from zero to the maximum rated voltage of the CT. This should be done slowly to avoid sudden surges of current that could damage the equipment.

  4. Record Data:

    • At each voltage increment (e.g., every 5 V), record the magnetizing current from the ammeter. Continue until the maximum voltage is reached or the readings show saturation.

  5. Plot the magnetization curve:

    • After you gather all the data, plot the magnetizing current (Y-axis) against the applied voltage (X-axis) on a graph. This plot will represent the excitation or magnetization curve of the CT.

Identifying Core Saturation and Other Issues

The excitation test of Current Transformer must identify signs of core saturation and other issues. Here’s how to interpret the results and what to look for:

  1. Identifying Core Saturation:

    • Saturation Point: As you plot the magnetization curve, find where it flattens. This shows the core has reached saturation. Beyond this point, a higher voltage will only slightly increase the magnetizing current.

    • Curve Behavior: A sharp rise in magnetizing current, with a slight rise in voltage, indicates saturation.

  2. Interpreting the Curve:

    • Normal Behavior: A steep, well-defined curve shows the CT core is healthy. It works correctly, without premature saturation.

    • A flat or distorted curve may mean core damage, material degradation, or manufacturing issues. Further investigation is necessary.

  3. Thermal Issues:

    • Monitor the temperature of the CT during the test of Current Transformer. If the CT overheats, it may not be transferring magnetic energy. This could be due to saturation or other issues.

  4. Quality Control:

    • Use the excitation test results as part of your quality control process. If many CTs show abnormal behavior on the excitation curve, it may indicate a problem with the materials or manufacturing.

  5. Action Steps:

  • If saturation is found, consider replacing the CT. Or, re-evaluate its use to ensure it meets the electrical system’s needs. If there are frequent saturations during operation, adjust the relay settings.

Type Test of Current Transformers

Type test of Current Transformer check if a current transformer model can withstand specified conditions. These tests are done in a controlled environment, usually at the manufacturer’s facility. This ensures that the CT can perform reliably under the expected operating stresses. These tests are tougher than routine ones. They are vital for long-term reliability.

Accuracy Test of Current Transformer

Accuracy is one of the most critical parameters for a current transformer. It must provide precise, current measurements. This ensures that metering and protective systems work correctly. The accuracy test of Current Transformer checks the CT’s ability to maintain its rated transformation ratio at various primary currents.

Procedure: The CT is subjected to a range of currents, typically from 10% to 120% of its rated value. The output in the secondary winding is then measured and compared to the expected value. The accuracy class of the CT is the difference between the actual and expected values. It must comply with standards like IEC 61869-2.

Temperature RiseTest of Current Transformer

This test of Current Transformer checks a transformer’s ability to handle thermal stress under normal conditions. Excessive heat can cause the insulation to degrade, affecting both performance and lifespan.

Procedure: Run the CT at its rated current for about 8 hours. This will let it reach its steady-state temperature. Then, the rise in temperature is measured. It is compared to the maximum allowable limit set by industry standards.

Short-Time Current Test of Current Transformer

This test of Current Transformer checks if the CT can withstand high fault currents for a short time without damage. In the real world, a power system may have short circuits. The CT must tolerate these without losing accuracy or failing.

Procedure: A high fault current, usually several times the rated current, is passed through the CT for a short period, usually one second. We then test the transformer’s performance. It must be accurate and undamaged.

Read more: Arc voltage in Circuit Breaker

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top